The Chartered institution of
Building Services Engineers Product Data Template |
Low Voltage Surge Protection Devices | |||
| Template Category | Low Voltage Surge Protection Devices (SPD) | |||
| Template Version | v1 | |||
| Category Description | Low voltage surge protection devices for indirect and direct effects of lightening or other transient overvoltages | |||
| Classification | Pr_65_72_27_48 | |||
| Classification System | UniClass2015 | |||
| Suitability for Use | Approved | |||
| Template Custodian | BEAMA | |||
| Information Category | Parameter Name | Value | Units | Notes |
| Manufacturer Data | ||||
| COBie Data | Manufacturer | Text | This is a COBie field, other fields will be required in final PDTs |
|
| Specifications | Manufacturer Website | URL | ||
| Specifications | Product Range | Text | ||
| Specifications | Product Model Number | Text | Or Code |
|
| Specifications | CE Mark | Text | Number, Yes, No |
|
| Specifications | UKCA Mark | Text | UKCA Mark |
|
| Specifications | Product Literature | URL | ||
| Specifications | Product Datasheet | URL | ||
| COBie Data | Features | Text | This is a COBie field, other fields will be required in final PDTs |
|
| Construction Data | ||||
| Specifications | Type | Text | This is a COBie field, other fields will be required in final PDTs |
|
| COBie Data | Shape | Text | This is a COBie field, other fields will be required in final PDTs |
|
| COBie Data | Material | Text | This is a COBie field, other fields will be required in final PDTs |
|
| COBie Data | Colour | Text | This is a COBie field, other fields will be required in final PDTs |
|
| COBie Data | Finish | Text | This is a COBie field, other fields will be required in final PDTs |
|
| Specifications | Terminal Type | Enumeration | Screw Or Screwless Or Plug-in Or Other |
|
| Specifications | Mounting Type | Enumeration | ||
| Specifications | Replaceable Modules | Y/N | Yes, No |
|
| Specifications | Number of Ports | Enumeration | 1, 2 |
|
| Specifications | Accessibility of Status Indicators | Enumeration | Accessible, inaccessible |
|
| Dimensional Data | ||||
| Specifications | Overall Depth | mm | Maximum depth of panel |
|
| Specifications | Overall Width | mm | Minimum and maximum widths available |
|
| Specifications | Overall Height | mm | Minimum and maximum heights available |
|
| Specifications | Gross Weight | kg | Equates to Operating Weight |
|
| Specifications | Shipping Weight | kg | Equates to dry weight of unit plus packaging allowance |
|
| Performance Data | ||||
| Specifications | Maximum Ambient Temperature | DegC | Numerical data with + or - e.g. +40 |
|
| Specifications | Minimum Ambient Temperature | DegC | Numerical data with + or - e.g. -5 |
|
| Specifications | Maximum Humidity | Number | Numerical data e.g 95% or 100% |
|
| Specifications | Minimum Humidity | Number | Numerical data e.g 5% |
|
| Specifications | Has Visual Indicator | Y/N | ||
| Specifications | Protection Function | Enumeration | Thermal, Leakage current or Overcurrent |
|
| Specifications | SPD Failure Behaviour | Enumeration | Open circuit or Short circuit |
|
| Specifications | IP Rating | Text | E.g. IP2X |
|
| Electrical Data | ||||
| Specifications | Frequency | Hertz | eg. NA, DC, 50,60, Other, UserDefined |
|
| Specifications | Supply Phase | Number | 1, 3 |
|
| Specifications | Maximum Backup Fuse or MCB | Number | e.g. 16A, 32A |
|
| Specifications | Voltage Protection Level | Number | e.g. 3kV, 6kV, 10kV…(Up) |
|
| Specifications | Rated Load Current IL | Number | Declared value |
|
| Specifications | Test Class | Enumeration | E.g. Type 1, Type 2 or Type 3 |
|
| Specifications | SPD Design | Enumeration | Voltage Switching, Voltage limiting or combination |
|
| Specifications | Protection Function | Enumeration | Thermal, Leakage current or Overcurrent |
|
| Specifications | SPD Failure Behaviour | Enumeration | Open circuit or Short circuit |
|
| Specifications | Impulse Discharge Current - Type 1 only Iimp | Number | 1 to 25 kA |
|
| Specifications | Impulse Discharge Current - Type 1 only Q | Number | 0.5 to 12.5 As |
|
| Specifications | Impulse Discharge Current - Type 1 only W R | Number | 0.25 to 156 kJ/Ohms |
|
| Specifications | Nominal Discharge Current - Type 2 only | Number | 0.05 to 20 kA |
|
| Specifications | Open Circuit Voltage - Type 3 only Uoc | Number | 0.1 to 20 kV |
|
| Specifications | Maximum Continuos Operating Voltage - Uc | Number | 45 to 2000 V |
|
| Specifications | Short Circuit Current Rating - ISCCR | Number | Declared value |
|
| Specifications | Follow Current Interupt Rating - Ifi | Number | Declared value |
|
| Specifications | Residual Current - IPE | Number | Declared value |
|
| Specifications | Transient Surge Current Rating - Itrans | Number | Where applicable |
|
| Specifications | Temporary Overvoltage Rating - UT | Number | Declared value |
|
| Specifications | Total Discharge Current - Itotal | Number | Declared value |
|
| Specifications | Voltage Drop - 2 port SPDs | V | Where applicable (Volts) |
|
| Specifications | Load-side Surge Withstand Capability - 2 port SPDs | Number | Where applicable (Amps) |
|
| Specifications | Voltage Rate of Rise - du dt | Number | Where applicable |
|
| Application Data | ||||
| Specifications | Reference Standard | Text | ||
| Sustainability | ||||
| Sustainable Material BREEAM etc | Embodied Carbon | kgCO2e | Awaiting Industry Standard |
|
| Sustainable Material BREEAM etc | Life Cycle Analysis | Number | Awaiting Industry Standard |
|
| Sustainable Material BREEAM etc | Location of Manufacturer | GridRef | Awaiting Industry Standard |
|
| Sustainable Material BREEAM etc | Green Guide for Specification | Text | Awaiting Industry Standard |
|
| Sustainable Material BREEAM etc | Environmental Product Declaration | Text | 3rd Party Verification |
|
| Sustainable Material BREEAM etc | Product Environmental Profile | Text | 3rd Party Verification |
|
| Sustainable Material BREEAM etc | CIBSE TM65 | Y/N | Only if an EPD or PEP is not available |
|
| Sustainable Material BREEAM etc | Responsible Sourcing of Materials | Text | Awaiting Industry Standard |
|
| Sustainable Material ETL | Energy Technology List | URL | Hyperlink to ETL webpage for product |
|
| Sustainable Material LEED v.4 | Responsible Extraction of Materials | Text | Awaiting Industry Standard |
|
| Sustainable Material LEED v.4 | Material Ingredient Reporting | Text | Awaiting Industry Standard |
|
| Operations & Maintenance | ||||
| Facilities/Asset Management | Operation and Maintenance Manual | URL | Hyperlink to Manufacturer O&M Data |
|
| Facilities/Asset Management | Daily | Text | Maintenance tasks or SFG20 codes |
|
| Facilities/Asset Management | Weekly | Text | Maintenance tasks or SFG20 codes |
|
| Facilities/Asset Management | Monthly | Text | Maintenance tasks or SFG20 codes. If Not Applicable Mark '0' |
|
| Facilities/Asset Management | Quarterly | Text | Maintenance tasks or SFG20 codes |
|
| Facilities/Asset Management | 6 Monthly | Text | ||
| Facilities/Asset Management | Annually | Text | ||
| Facilities/Asset Management | Bespoke Timeframe | Text | Maintenance tasks or SFG20 codes |
|
| Facilities/Asset Management | Expected Life | Years | ||
| Facilities/Asset Management | Warranty ID | Text | ||
|
This schedule is the property of CIBSE although it can be freely used in the ways described, and completed with data specific to particular products. It is important that the Categories and Parameters given on the form are not changed. It is also important that where units of measurement are defined on the form that these too are followed. Any comment or suggestion on their revision should be addressed to pdt@cibse.org |
||||
|
©CIBSE 2015
©The Chartered Institution of Building Services Engineers www.cibse.org
| ||||